HVAC Danfoss energy regulators Danfoss energy regulation adjusting,Danfoss hot gas bypass valve KVC Series Danfoss KVC Danfoss energy regulators Danfoss hot gas bypass valve Danfoss Capacity Regulators A capacity regulator is used for the adaption of the compressor Capacity to the actual...
Product description

HVAC Danfoss energy regulators Danfoss energy regulation adjusting,Danfoss hot gas bypass valve KVC Series

Danfoss KVC

Danfoss energy regulators

Danfoss hot gas bypass valve

 

Danfoss Capacity Regulators

 

A capacity regulator is used for the adaption of the compressor Capacity to the actual evaporator load.

 

They are placed in a by-pass between high and low pressure sides Of the refrigeration plant.

 

In this position they impose a downward Limit on the compressor suction pressure by supplying the low Pressure side with replacement duty in the form of hot gas/cool Gas from the high-pressure side.

 

Regulating range 0.2 - 6.0 bar, factory setting 2 bar, max. working pressure 28 bar.

 

KVC type energy regulator is for regulating capacity of the compressor, to adapt to the evaporator load.

 

KVC type energy regulator is mounted on the refrigeration system of high / low pressure side of the road between the bypass pipe.

KVC helps to send the heat from high pressure side into the lower pressure side through the bypass line, to replace part of the load, so that the compressor suction pressure is not less than the minimum limit.

 

Danfoss capacity regulators are used to adapt compressor capacity to actual evaporator load by supplying a replacement capacity in the form of hot/cool gas.

 

They are installed in a bypass line between the high and low-pressure sides of the refrigeration system and are designed for direct gas injection into the suction line.

 

693723 impose a lower limit on the compressor suction pressure by supplying the low pressure side with replacement capacity in the form of hot gas/cool gas from the high pressure side.

 

◆ KVC energy regulator is used to adjust the compressor cooling capacity, so that it is compatible with the evaporator load 

◆ KVC energy regulator installed in the cooling system between the high / low side of the bypass pipeline 

◆ KVC through the bypass line of high-pressure side of the hot air into the low side instead of part of the load, so that the compressor suction pressure is not less than the minimum limit

 

Product Features: 

◆ To achieve precise and variable pressure regulation

◆ Application cooling capacity and wide operating range

◆ Pulsation damping design

◆ Stainless steel to bellows

◆ "closed" brazing structure

◆ Compact angle form of design, easy to install in any location

◆ provide a wide range of size of the bell mouth and outer diameter welding interface

◆ can be used for CFC, HCFC and HFC refrigerant

 

Please find more information from below list:

Type
Rated capacity
Solder connection
Code no.
R22
R134a
R404A/R507
R407C
( inch)
KVC12
7.6
4.8
6.9
8.4
 
1/2
034L0143
KVC15
14.9
9.4
13.6
16.4
 
5/8
034L0147
KVC22
19.1
12
17.4
21
 
7/8
034L0144

Danfoss MODEL KVC
Part Number
Model Number
Regulating
Connections
Rated Capacity (kW)
Range kPa (psig)
R22
R134a
R404A
R407C
Capacity Regulator (hot gas Bypass)
034L0141
KVC12
20 to 600 (3 to 87)
1/2" Fl.1
7.6
4.8
6.9
8.4
034L0042
KVC15
5/8" Fl 1
14.9
9.4
13.6
16.4
034L0043
KVC12
1/2" ODS
7.6
4.8
6.9
8.4
034L0147
KVC15
5/8" ODS
14.9
9.4
13.6
16.4
034L0144
KVC22
7/8" ODS
19.1
12
17.4
21

Welcome to wholesale the high quality and precise hvac danfoss energy regulators danfoss energy regulation adjusting,danfoss hot gas bypass valve kvc series in stock from our factory. As one of the leading manufacturers and suppliers in China, we can assure you the good quality of our products. Check the price list and the quotation with us.